DCC2
Project image

  • Clear display and easy operation with LED displays and operation keys
  • Connection possibility for 2 conventional zones for the use with the CT 3000 fire detection components with up to 20 detectors per zone
  • Integrated power supply according to EN 54-4: 1997/A2: 2006 with 1 output for external devices rated at 24 V DC
  • Independent connection of detector and signalling device zones
  • Integrated "one-man-revision mode"
  • Manual control of signalling devices via seperate input
  • Supply Voltage: 230 V AC ( ±10 %)
  • Emergency Supply: 1 x 12 V / 7 Ah
  • Quiescent Current: 2 mA to 10 mA
  • Alarm Current: 10 mA to 110 mA
  • Output: 2 x 24 V/300 mA monitored for alarming devices; 2 Relay outputs 60 V DC/120 V AC/3 A for alarm and fault
  • Ambient Temperature: -5°C to +40°C
  • Operating Temperature: -5°C to +40°C
  • Storage Temperature: -20°C to +60°C
  • Humidity: max. 95%
  • Protection class: IP 30
  • Dimensions (H x W x D): 288 mm x 340 mm x 98 mm
  • Weight: 2,3 kg (w/o battery)
  • Material: ABS, Glass
  • Colour: light grey RAL 7035
  • Standards: EN 54-2: 1997/A1: 2006; EN 54-4: 1997/A2: 2006
  • CE-CPD-Number: 1293-CPD-0174
  • Further Approvals: EVPÜ
  • Display: 21 LED-for status messages, thereof 11 LEDs covered; 6 keys for operation