PL-3301 O W
Project image

  • Exact pollution recognition by an additional independent measuring chamber
  • Detector sensitivities automatically calibrated and freely programmable
  • Fault monitoring of the measurement chamber signal and Loop 3000-electronics
  • Periodic sensor test
  • Automatic and manual addressing with Loop 3000
  • Integrated Isolator and T-branch option
  • Functions completely integrated via Loop 3000-protocol
  • Storage of last maintenance date
  • Self learning modes for the ambient conditions
  • Storage of last maintenance date
  • Multicolour LED for alarm (red) and fault (yellow)
Technical Data
  • Supply Voltage 15 V to 34 V DC (2-wire bus)
  • Quiescent Current 280 μA
  • Alarm Current 5 mA
  • Output OC: max. 10 mA for parallel indicator or buzzer
  • Protection class IP 40
  • Ambient temperature -10°C to +60°C
  • Humidity max. 95%
  • Sensitivity Adjustable in 5 sensitivity levels
  • Dimensions (H x D) appr. 47 mm x 110 mm
  • Material Metal cover, ABS
  • Standards DIN EN 54-7, EN 54-17
  • VDS-approval G 205046
  • System-approval S 210001, S 216001
  • CE-CPD-Number 0786-CPD-20037
  • CE-CPR-Number 0786-CPR-20037