PL-3300 COBT
- Alarm evaluation with professional CO-sensor technology
- Measurement of carbon monoxid with 2 alarm thresholds: Prealarm: 15 ppm in 15 min Alarm: 30 ppm in 60 min
- Integrated acoustic indication for CO-pre alarm and CO-alarm
- Highest reliability by intelligent combination of thermal and CO sensor via algorithm
- Integrated temperature measurement as rate of rise procedure and maximum value in accordance to EN 54-5 1A
- Periodic sensor test
- Automatic and manual addressing with Loop 3000
- Integrated Isolator and T-branch option
- Functions completely integrated via Loop 3000-protocol
- Freely programmable sensitivity levels for presence/absence
- Mapping of a temperature profile of the panel
- Multicolour LED for alarm (red) and fault (yellow)
Technical Data
- Supply Voltage 15 V to 34 V DC (2-wire bus)
- Quiescent Current 600 μA
- Alarm Current 5 mA
- Output OC: max. 10 mA for parallel indicator or buzzer
- Protection class IP 40
- Ambient temperature -10°C to +60°C
- Humidity max. 95%
- Sensitivity CO-Alarm: at 30 ppm, Heat EN 54-5 1A
- Dimensions (H x D) 52 mm x 100 mm
- Material ABS, Glass
- Colour White (similar to RAL 9003)
- Standards DIN EN 54-5, EN 54-17
- VDS-approval G 207005
- System-approval S 210001, S 216001
- CE-CPD-Number 0786-CPD-20582
- CE-CPR-Number 0786-CPR-20582
- Remarks For further information to operation and maintenance please refer to manual (part-no. 51481)