PL-3300 COBT
Project image

  • Alarm evaluation with professional CO-sensor technology
  • Measurement of carbon monoxid with 2 alarm thresholds: Prealarm: 15 ppm in 15 min Alarm: 30 ppm in 60 min
  • Integrated acoustic indication for CO-pre alarm and CO-alarm
  • Highest reliability by intelligent combination of thermal and CO sensor via algorithm
  • Integrated temperature measurement as rate of rise procedure and maximum value in accordance to EN 54-5 1A
  • Periodic sensor test
  • Automatic and manual addressing with Loop 3000
  • Integrated Isolator and T-branch option
  • Functions completely integrated via Loop 3000-protocol
  • Freely programmable sensitivity levels for presence/absence
  • Mapping of a temperature profile of the panel
  • Multicolour LED for alarm (red) and fault (yellow)
Technical Data
  • Supply Voltage 15 V to 34 V DC (2-wire bus)
  • Quiescent Current 600 μA
  • Alarm Current 5 mA
  • Output OC: max. 10 mA for parallel indicator or buzzer
  • Protection class IP 40
  • Ambient temperature -10°C to +60°C
  • Humidity max. 95%
  • Sensitivity CO-Alarm: at 30 ppm, Heat EN 54-5 1A
  • Dimensions (H x D) 52 mm x 100 mm
  • Material ABS, Glass
  • Colour White (similar to RAL 9003)
  • Standards DIN EN 54-5, EN 54-17
  • VDS-approval G 207005
  • System-approval S 210001, S 216001
  • CE-CPD-Number 0786-CPD-20582
  • CE-CPR-Number 0786-CPR-20582
  • Remarks For further information to operation and maintenance please refer to manual (part-no. 51481)